Bldg 650 Vault Upgrade

Notice ID: FA520925Q9029

Vendor shall remove and dispose of existing desks, chairs, communication racks, carpet, 
electrical/comm. wiring and floor tiles. The vendor shall install 10”H raised floor with ramps. The vendor shall 
design and install all electrical cables incorporating 1st floor gear box, main panel, sub panel, UPS, CRAC Units, 14 
communication racks (A&B), shut off switch, lights, alarm system, and environmental alarm (utilize drawings and 
equipment list). The vendor shall install two 20T CRAC Units (A&B), that alternate when cooling w/under floor 
venting (utilize vent drawing) and drainage. The vendor shall install two 100KVA UPS including power cables, 
grounding, power panels, (A&B) power to each rack, PDUs, under floor ladder rack (utilize drawings). The vendor 
shall install 14 communication racks, 1 half rack, grounding, power and above rack cable wire management basket
(utilize drawings). The vendor shall install emergency shut off switch, environment monitoring, ISP fiber optic 
distribution cables (rm to rm), rack interconnect fiber cables (rack to hub rack). 

Department/Ind.Agency DEPT OF DEFENSE
Subtier DEPT OF THE AIR FORCE
Office PACIFIC AIR FORCES